DA-P 10-260/T-EN54

DA-P 10-260/T-EN54

  • quick mounting
  • high impact ABS plastic
  • PG7 cable gland
DA-P 10-260/T-EN54

Sturdy sound projector for voice alarm applications, certified according to EN 54-24, suitable for voice announcements and background music with excellent sound quality in buildings.

The 10W-powered bi-directional speaker is equipped with two 130mm full-range loudspeakers and a 100V line transformer with 3 power adjustments. A robust ABS plastic housing in RAL 9016 and a solid aluminium mounting bracket ensure the permanent installation of this speaker.

For additional reliability, a ceramic block and a thermal fuse are provided in a junction box and the speaker chassis is impregnated against wetness.

The speaker is compliant with the British Standard BS 5839, Part 8.

Article No.: 20173235
ProductDA-P 10-260/T-EN54
Power 10/5/2,5 W
Impedance (100V) 1000/2000/4000 ohm
Information Frequency Range 100 - 20.000 Hz
Information Frequency Response 90 - 25.000 Hz
Information SPL 1W/1m, peak 90,7 dB
Information SPL 1W/4m, peak 78,7 dB
Information SPL Pmax/4m, peak 88,7 dB
SPL IEC268-5, 1W/1m 85,0 dB
SPL EN54-24, Pmax/4m 82,5 dB
Information Sensitivity EN54-24, 1W/1m 85,6 dB
Information Sensitivity EN54-24, 1W/4m 73,0 dB
Dispersion -6dB, 500Hz h / v 2x130° / 2x130°
Dispersion -6dB, 1KHz h / v 2x170° / 2x170°
Dispersion -6dB, 2KHz h / v 2x160° / 2x160°
Dispersion -6dB, 4KHz h / v 2x65° / 2x65°
Connector ceramic block
Temperature range -25 / +70 C°
Dimensions 202 x 163 x 170 mm
Type A/B B
IP Rating IP56
Weight (net) 1,82kg
Colour RAL 9016
Mounting Mounting bracket
Packing Unit 8
Ref. Nr. 020-17
ID-Code SAA-LS20
Certificate Number 1438-CPR-0388
CE Year 17
BS5839 EN 54-24 Outside Application IP56 UV Protected Weather proof Measurements
ic audio loudspeakers are tested and classified according to the IEC standard 60529 (degree of protection by enclosure) against the penetration of foreign objects and moisture. The classification is conforming to standards through characterization with a fixed code. This code consists of the letters IP (International Protection) followed by two digits. The first digit indicates the degree of protection against dust and the second digit the degree of protection against water. Please note that the testing of the products has been carried out in laboratory conditions which are not always 100% comparable with the conditions of different installation environments. This protection can be reduced due to normal wear and tear depending on the installation environment.
RoHS compliant (2011/65/EU)
The IP rating as well as the temperature range specified are based on ic audio test results, not on CNBOP-PIB test results. Certification only verifies the minimum requirements for EN54-24 compliance.
Technical Drawing
Sensitivity
SPLmax
DA-P 10-260/T-EN54
Isobar
DA-P 10-260/T-EN54
Polar Diagram 500Hz
DA-P 10-260/T-EN54
Polar Diagram 1000Hz
DA-P 10-260/T-EN54
Polar Diagram 2000Hz
DA-P 10-260/T-EN54
Polar Diagram 4000Hz
DA-P 10-260/T-EN54
Polar Diagram 8000Hz