EN54
TH-100-EN54
barcode 4 260590 180100

Horn speaker for Voice Alarm, 100W power, certified EN 54-24

Technical Data
Colour black
Dimensions 1228 x 832 x 413 mm
Dispersion -6dB, 500Hz h=58° v=35°
Dispersion -6dB, 1KHz h=35° v=25°
Dispersion -6dB, 2KHz h=40° v=20°
Dispersion -6dB, 4KHz h=54° v=15°
Sensitivity EN54-24, 1W/1m 113,9 dB
Sensitivity EN54-24, 1W/4m 101,0 dB
Frequency Range 280 - 9.000 Hz
Frequency Response 250 - 10.000 Hz
SPL IEC268-5 , 1W/1m 113,0 dB
SPL EN54-24, Pmax/4m 119,0 dB
Power 100/50/25W
EN54
TH-100-EN54
barcode 4 260590 180100
Mounting Instruction

Mounting TH-100-WH

  1. Attach two mounting brackets each (WH left and WH right) to the ceiling using suitable fixing material. The TH-100-WH brackets are not included in the delivery.
  2. Then fix the speaker to the brackets with the M8x20 screws and the M8 washers. Please use a torque of 16 Nm for tightening the screws of the bracket.
  3. Feed the loudspeaker cable through the PG gland and connect the cable to the ceramic clamp, according to the required power (see imprint on the clamp).
  4. Place the cover on the horn driver and fix it with the screws M8x25 and the steel and rubber washers M8.
  5. Tighten the screws of the rear cover of the horn driver in 2 steps:
    1. Tighten all 8 screws with a torque of 2.0 Nm.
    2. Retighten the screws with 2.0 Nm.

Mounting TH-100-PH

Should you use the TH-100-PH premium mounting, please refer to the corresponding installation drawings.

 

Safety note: Due to the weight of the product, we recommend that the installation is carried out by 2 people.

TH-100-WH
TH-100-WH
TH-100-PH
TH-100-PH
TH-100-PH